SERVICE MANUAL
KML “F” SERIES
KML “H” SERIES
MODELS
NO.:
ISSUED:
REVISED:
AUG. 18, 1999
JAN. 13, 2004
73085
Przeglądanie stron 0
1 2 3 4 5 6 ... 108 109

Podsumowanie treści

Strona 1 - KML “H” SERIES

HOSHIZAKIMODULAR CRESCENT CUBERSERVICE MANUALKML “F” SERIESKML “H” SERIESMODELSNO.:ISSUED:REVISED:AUG. 18, 1999JAN. 13, 200473085

Strona 2

105. KML-350MAH

Strona 3 - CONTENTS

10011. REMOVAL AND REPLACEMENT OF THERMISTORCAUTION1. Fragile, handle very carefully.2. Always use a recommended sealant (High Thermal Conductive Type

Strona 4

10110) Secure the insulation using the Plastic Cable Ties.11) Connect the Thermistor leads through the bushing of the Control Box to the K3Connector o

Strona 5

10213. REMOVAL AND REPLACEMENT OF WATER VALVE1) Turn off the power supply.2) Close the Water Supply Line Shut-off Valve.3) Remove the Front Panel.4) R

Strona 6 - 1. KML-250MAH

10315. REMOVAL AND REPLACEMENT OF SPRAY TUBES1) Turn off the power supply.2) Remove the Front Panel and the Insulation Panel.3) Remove the Rubber Hose

Strona 7 - 2. KML-250MWH

104VI. MAINTENANCE AND CLEANING INSTRUCTIONSIMPORTANTEnsure all components, fasteners and thumbscrews are securely in place afterany maintenance or c

Strona 8 - 3. KML-350MAF

105[2] Remove the water from the potable water supply line:1) Turn off the power supply and remove the Front Panel.2) Move the Control Switch, on the

Strona 9 - 4. KML-350MWF

106MODEL WATER "SCALE AWAY" WATER SANITIZERgal. fl. oz. gal. fl. oz.KML-250 2 10.5 2 1KML-350 2 10.5 2 1KML-450 2 10.5 2 1KML-600 2.5 13.5 2

Strona 10 - 5. KML-350MAH

1075) Place the Control Switch in the “SERVICE” position. Then place the Service Switch in the “DRAIN” position.6) Replace the Front Panel and tur

Strona 11

1083. SANITIZING PROCEDURE - Following Cleaning Procedure1) Dilute a 5.25% Sodium Hypochlorite solution (chlorine bleach) with water (Add 1.0 fl.

Strona 12

1094. MAINTENANCEIMPORTANTThis icemaker must be maintained individually, referring to the instructionmanual and labels provided with the icemaker.1) S

Strona 13 - 8. KML-450MAF

116. KML-350MWH (Beginning serial #L00001J, ending Serial #M20060C)

Strona 14 - 9. KML-450MWF

127. KML-350MWH (Beginning serial #M30061E)

Strona 16

149. KML-450MWF

Strona 17

1510. KML-450MAH

Strona 18 - 13. KML-600MAF

1611. KML-450MWH (Beginning Serial #L00001D, ending Serial #M10530B)

Strona 19 - 14. KML-600MWF

1712. KML-450MWH (Beginning Serial #M20531D)

Strona 22

2IMPORTANTOnly qualified service technicians should attempt to service or maintain this icemaker.No service or maintenance should be undertaken until

Strona 23

2015. KML-600MRF

Strona 25 - Unit: mm. (inches)

2217. KML-600MWH (Beginning Serial #L00001D, ending Serial #M10115C)

Strona 26 - SPECIFICATIONS

2318. KML-600MWH (Beginning Serial # M10121E)

Strona 28

2520. CONDENSER UNITURC-7FUnit: mm. (inches)

Strona 29

26SPECIFICATIONSURC-7F

Strona 30

27II. GENERAL INFORMATION1. CONSTRUCTION[a] KML-250MAH, KML-350MAF, KML-350MAH, KML-450MAF, KML-450MAHSpray TubesWater SupplyInletJunction BoxCondens

Strona 31

28[b] KML-250MWH, KML-350MWF, KML-350MWH, KML-450MWF, KML-450MWHSpray TubesWater SupplyInletJunction BoxControl BoxDrierHot Gas ValveCompressorWaterRe

Strona 32 - 2. CONTROLLER BOARD

29Spray TubesWater SupplyInletJunction BoxCondenserCondenserFan MotorControl BoxDrierHot Gas ValveCompressorFloat SwitchControl SwitchWater PumpExpans

Strona 33

3 • Please review this manual. It should be read carefully before the icemaker is servicedor maintenance operations performed. Only qualified servi

Strona 34 - Machines

30[d] KML-600MWF, KML-600MWHSpray TubesJunction BoxWaterRegulatorControl BoxDrierHot Gas ValveFloat SwitchControl SwitchWater PumpExpansionValveCompre

Strona 35

31[e] KML-600MRF, KML-600MRHSpray TubesJunction BoxReceiverTankControl BoxDrierHot Gas ValveFloat SwitchControl SwitchWater PumpExpansionValveCompress

Strona 36 - 1st Cycle

322. CONTROLLER BOARD[a] SOLID-STATE CONTROL1) A HOSHIZAKI exclusive solid-state control is employed in Modular Crescent Cubers.2) A Printed Circuit B

Strona 37

332) Defrost TimerThe defrost cycle starts when the Float Switch opens and completes the freeze cycle.But the Defrost Timer does not start counting un

Strona 38

34The green LED’s 1-4 represent the corresponding relays and energize and sequence 5seconds from initial start-up as follows:Sequence Step LED’s on L

Strona 39

35(Control Products HOS-001A Board)The application switch located between relay X3 & X4 must be set to match the originalboard application. Place

Strona 40

36[c] SEQUENCE1st Cycle1. Unit energized and Control Switch to “ICE” position. Water supply cycle starts.2. After 1 minute, Defrost cycle start

Strona 41

372nd Cycle and after with pump drainIMPORTANTFreeze cycle time is limited to 60 minutes evenif Float Switch does not open.1. Float Switch opens and s

Strona 42

38IMPORTANTFreeze cycle time is limited to 60 minutes evenif Float Switch does not open.2nd Cycle and after with no pump drain1. Float Switch opens an

Strona 43

39[d] CONTROLS AND ADJUSTMENTSThe Dip Switch is factory-adjusted to the following positions:FOR MODELS WITH THERMOSTAT:Switch Nos. 1 and 2:Used for ad

Strona 44 - 3. SWITCHES

4III. TECHNICAL INFORMATION...471. WATER CIRCUI

Strona 45 - 4. MECHANICAL BIN CONTROL

401) Defrost ControlA thermistor (Semiconductor) is used for a defrost control sensor. The resistancevaries depending on the Suction Line temperature

Strona 46

413) Drain TimerThe Drain Timer is factory-adjusted, and no adjustment is required.SETTING TIMEDip Switch Dip SwitchNo. 3 No. 4 T1 T2OFF OFF 10 second

Strona 47 - III. TECHNICAL INFORMATION

426) Bin ControlMODELS WITH THERMOSTATCAUTIONWhen the ambient temperature is below 45°F, the Bin Control Thermostatoperates to stop the icemaker even

Strona 48 - KML-600MWF, KML-600MWH

43(iv) After Step (iii), de-energize the unit and confirm that the Defrost Timer is in theminimum position. Disconnect the resistor from the Controll

Strona 49 - [c] KML-600MRF, KML-600MRH

443. SWITCHESTwo control switches are used to control operation in the KML Series Modular CrescentCubers. These switches are referred to as the “Cont

Strona 50 - 2. WIRING DIAGRAMS

454. MECHANICAL BIN CONTROL (THESE INSTRUCTIONS NOT APPLICABLE TO MODELS WITH THERMOSTAT)[a] PROXIMITY SWITCH1) This machine uses a lever-actuat

Strona 51

46[c] TROUBLESHOOTING (MECHANICAL BIN CONTROL ONLY)1) Machine will not start(i) Move dip switch No. 7 to the “OFF” position. If the machine starts

Strona 52 - [c] KML-350MAF and KML-350MWF

47III. TECHNICAL INFORMATION1. WATER CIRCUIT AND REFRIGERANT CIRCUIT[a] KML-250MAHKML-350MAF, KML-350MAHKML-450MAF, KML-450MAHKML-600MAF, KML-600MAH

Strona 53

48[b] KML-250MWHKML-350MWF, KML-350MWHKML-450MWF, KML-450MWHKML-600MWF, KML-600MWH

Strona 54

49[c] KML-600MRF, KML-600MRH

Strona 55 - [f] KML-450MAF and KML-450MWF

5[h] KML-450MAF ...72[i] KML-45

Strona 56

502. WIRING DIAGRAMS[a] KML-250MAH (Beginning Serial #L00001E, ending Serial #M10460F; KML-250MWH (Beginning Serial #L10001K, ending Seri

Strona 57

51Note: KML-250MAH Pressure SwitchCut-out 412.5 PSIGCut-in 327 ± 21.3 PSIG[b] KML-250MAH (Beginning Serial #M20461G); KML-250MW

Strona 58

52[c] KML-350MAF and KML-350MWFNote: KML-350MAF Pressure SwitchCut-out 412.5 PSIGCut-in 327 ± 21.3 PSIGKML-350MWF Pressure SwitchCut-out

Strona 59

53[d] KML-350MAH (Beginning Serial #L00001L, ending Serial #M10290F); KML-350MWH (Beginning Serial #L00001J, ending Serial #M30080F)Note: KML

Strona 60

54[e] KML-350MAH (Beginning Serial #M20291G); KML-350MWH (Beginning Serial #M40081G)Note: KML-350MAH Pressure SwitchCut-out 412.5

Strona 61

55Note: KML-450MAF Pressure SwitchCut-out 412.5 PSIGCut-in 327 ± 21.3 PSIG[f] KML-450MAF and KML-450MWFKML-450MWF Pressure SwitchCut-out

Strona 62

56[g] KML-450MAH (Beginning Serial #L00101C, ending Serial #L00950G); KML-450MWH (Beginning Serial #L00001D, ending Serial #L00200G)Note:

Strona 63 - 3. TIMING CHART

57[h] KML-450MAH (Beginning Serial #L20951H, ending Serial #M12770F); KML-450MWH (Beginning Serial #L10201H, ending Serial #M20710F)Note: KML

Strona 64 - From Freeze Cycle

58[i] KML-450MAH (Beginning Serial #M22771G); KML-450MWH (Beginning Serial #M30711G)Note: KML-450MAH Pressure SwitchCut-out 412.5 PS

Strona 65 - [a] KML-250MAH

59+21.3- 0+21.3- 0Note: KML-600MWF Pressure SwitchCut-out 384 PSIGCut-in 284.5 ± 21.3 PSIGKML-600MAF, MRF Pressure SwitchCut-out 412.5

Strona 66

6I. SPECIFICATIONS1. KML-250MAH

Strona 67 - [c] KML-350MAF

60[k] KML-600MAH (Beginning Serial #L00001F, ending Serial #L00070F); KML-600MWH (Beginning Serial #L00001D, ending Serial #L00080E); K

Strona 68 - [d] KML-350MWF

61[l] KML-600MAH (Beginning Serial #L10071H, ending Serial #M10460G); KML-600MWH (Beginning Serial #L10081K, ending Serial #M10140E); KML-60

Strona 69 - [e] KML-350MAH

62[m] KML-600MAH (Beginning Serial #M2_ _ _ _ _); KML-600MWH (Beginning Serial #M20141F); KML-600MRH (Beginning Serial #M20331E)Note: KM

Strona 70

63**3. TIMING CHARTControlSw. inICEBinThermo-stat ONPressureSw. ONOverheatProtectReset Hi Temp Mid Temp Lo Temp Too Lo Temp Normal Too Hi Temp

Strona 71

64To Stand-by Cycle (When Control Sw. is turned OFF, Pressure Sw. is OFF, Thermistor Temp. exceedst1, or Bin Control is in full position)To Freeze Cyc

Strona 72 - [h] KML-450MAF

654. PERFORMANCE DATA [a] KML-250MAH

Strona 75

68[d] KML-350MWF

Strona 76

69 [e] KML-350MAH

Strona 78 - [n] KML-600MWF

70[f] KML-350MWH (Serial #L00001J through M20060C)

Strona 79 - [o] KML-600MRF

71[g] KML-350MWH (Beginning Serial #M30061E)

Strona 81

73[i] KML-450MWF

Strona 82

74[j] KML-450MAH

Strona 83 - [s] KML-600MRH

75[k] KML-450MWH (Serial #L00001D through M10530B)

Strona 84 - 1. NO ICE PRODUCTION

76[l] KML-450MWH (Beginning Serial #M20531D)

Strona 85

77[m] KML-600MAF

Strona 86

78[n] KML-600MWF

Strona 89

80Strona KML-600MAH

Strona 90 - 2. BRAZING

81[q] KML-600MWH (Serial #L00001D through Serial #M10115C)

Strona 91

82[r] KML-600MWH (Beginning Serial #M10121E)

Strona 92

83[s] KML-600MRH

Strona 93

84 PROBLEM POSSIBLE CAUSE REMEDY[1] The icemaker a) Power Supply 1. “OFF” position. 1. Move to “ON” position will not start 2. Loose co

Strona 94

85 PROBLEM POSSIBLE CAUSE REMEDYl) Controller Board 1. Defective 1. See “II.2[e] CHECKING CONTROLLER BOARD.”[2] Water a) Float switch 1.

Strona 95

86 PROBLEM POSSIBLE CAUSE REMEDY[4] Water a) Water Solenoid 1. Diaphragm does not close. 1. Check for water leaks continues to Val

Strona 96

873. LOW ICE PRODUCTION PROBLEM POSSIBLE CAUSE REMEDY[1] Freeze cycle a) Float Switch 1. Leads short-circuit or 1. Check and replace.

Strona 97 - WATER-COOLED MODEL ONLY

88 PROBLEM POSSIBLE CAUSE REMEDY[1] Icemaker will a) Bin Control 1. Set too cold. 1. Adjust warmer. not stop when Thermostat 2. Def

Strona 98 - MODEL ONLY

89V. REMOVAL AND REPLACEMENT OF COMPONENTSIMPORTANTEnsure all components, fasteners and thumbscrews are securely in placeafter the equipment is servi

Strona 99

94. KML-350MWF

Strona 100 - Thermistor Lead Cable Tie

905) Disconnect the Vacuum Pump, and attach a Refrigerant Service Cylinder tothe High-side line. Remember to loosen the connection, and purge the airf

Strona 101

913. REMOVAL AND REPLACEMENT OF COMPRESSORIMPORTANTAlways install a new Drier every time the sealed refrigeration system is opened.Do not replace the

Strona 102

924. REMOVAL AND REPLACEMENT OF DRIERIMPORTANTAlways install a new Drier every time the sealed refrigeration system is opened.Do not replace the Drier

Strona 103

935. REMOVAL AND REPLACEMENT OF EXPANSION VALVEIMPORTANTSometimes moisture in the refrigerant circuit exceeds the Drier capacity andfreezes up at the

Strona 104 - IMPORTANT

946. REMOVAL AND REPLACEMENT OF HOT GAS VALVE AND LINEVALVECAUTIONAlways use a copper tube of the same diameter and length when replacingthe hot gas l

Strona 105

9510) Cut the leads of the Solenoid allowing enough lead length to reconnect using closed end connectors.11) Connect the new Solenoid leads.12)

Strona 106 - 2. CLEANING PROCEDURE

967. REMOVAL AND REPLACEMENT OF EVAPORATORIMPORTANTAlways install a new Drier every time the sealed refrigeration system isopened. Do not replace the

Strona 107

978. REMOVAL AND REPLACEMENT OF WATER REGULATING VALVE -WATER-COOLED MODEL ONLYIMPORTANTAlways install a new Drier every time the sealed refrigeration

Strona 108

989. ADJUSTMENT OF WATER REGULATING VALVE - WATER-COOLEDMODEL ONLYThe Water Regulating Valve (also called “WATER REGULATOR”) is factory-adjusted.No ad

Strona 109 - 4. MAINTENANCE

9910. REMOVAL AND REPLACEMENT OF CONDENSING PRESSURE REGULATOR (C.P.R.) - REMOTE AIR-COOLED MODEL ONLYIMPORTANTAlways install a new Drier every t