* Drain lines should not be piped directly to the sewer system. An air gap of a minimum of
2 vertical inches (5 cm) should be between the end of the drain pipes from the icemaker
and the floor drain.
* This icemaker should be installed in accordance with applicable national, state and local
regulations.
* A plumbing permit and services of a licensed plumber may be required in some areas.
Fig. 4
KM-201BAH
KM-260BAH
Water Supply Inlet
1/2” FPT
Drain Outlet
3/4” FPT
Shut-off Valve
To approved floor drain
Two-inch (5 cm)
air gap
Drain
Floor
Separate piping to approved drain.
Leave a two-inch (5 cm) vertical air
gap between the end of each pipe
and the drain.
Drain Valve
1/4” fall per foot